How to specify an IEC fuse holder

01

The holder carries part of the rating

An NH base, a cylindrical modular carrier, a BS88 holder or a D/D0 screw cap is what keeps the fuse voltage and breaking capacity in the circuit. A holder rated below the fuse voltage becomes the weak point.

02

Size rejects the wrong fuse

A 3-pole NH00 base does not accept an NH2 blade. A 10x38 mm carrier will not close on a 14x51 mm cartridge. D and D0 bottle fuses use different diameters and gauge rings.

03

What to put on the order

State the fuse size, number of poles, DIN-rail or screw mounting, and whether you need a blown-fuse microswitch. Some NH assemblies are bases only. Others are switch-disconnectors. The catalog number tells them apart.

Buyer questions

Questions buyers ask

Can I reuse the old holder with a higher-voltage fuse?

Only if the holder voltage and short-circuit rating are equal to or above the new fuse. Otherwise replace the holder with the fuse.

Do NH bases include a switch?

Some are bases only. Others are switch-disconnectors. Order the catalog number, not the family name.

Are D and D0 caps the same?

No. The diameters and gauge rings are different so the cap rejects the wrong amp size.