Eaton Bussmann Authorized Distributor | Certificate No. 56 | Valid Through: December 31, 2026

Low Voltage IEC Fuses

IEC low-voltage fuses: NH, cylindrical 10x38 to 22x58, BS88, and D/D0 bottle fuses for industrial distribution and motor circuits.

4 products

Selection guide

How to specify an IEC low-voltage fuse

01

Bodies in this range

This is the IEC side of Bussmann: NH blade fuses from size 000 to 4, cylindrical 10x38, 14x51 and 22x58 mm cartridges, BS88 offset-tag fuses, and D/D0 bottle fuses.

02

gG and aM are not interchangeable

gG protects cable against overload and short circuit. aM protects a motor against short circuit only and needs a separate overload relay. C10M is the aM motor version and is not a replacement for C10G.

03

C10G10 inside the cylindrical family

C10G10 is the 10 A, 500 V, gG member of the 10x38 mm family. Larger currents step up to 14x51 mm and 22x58 mm. The holder must be the same size and at least the same voltage.

Buyer questions

Questions buyers ask

Are NH and cylindrical fuses interchangeable?

No. NH uses blade contacts in an NH base. Cylindrical fuses use a ferrule holder.

Which standard applies?

IEC 60269. BS88 parts also follow BS 88. Confirm the utilization category on the barrel before ordering.

What has to match on a reorder?

Body size, voltage, amp rating and the gG or aM class. The holder stays with the same body.

Online RFQ Inquiry

Fill in your requirements. Our engineer will provide a quotation within 1 working day.
Bulk inquiry with BOM list is supported.