Eaton Bussmann Authorized Distributor | Certificate No. 56 | Valid Through: December 31, 2026

Industrial Motors and Drives

A drive fuse protects the semiconductors in the converter, not the building feeder. Square-body and semiconductor families on this site are published up to 1250 Vac. Ferrule high-speed fuses are published up to 700 Vac. The CCP disconnect isolates the circuit and is listed to UL 98 up to 400 A at 600 V.

01

Semiconductor, not feeder

A class J or NH fuse can feed the drive panel. The devices inside the drive need a high-speed fuse whose let-through the semiconductors can survive.

02

Body style

Ferrule, square body, and British standard high-speed fuses do not share a holder. Match the body, then the voltage and current.

03

Isolation

CCP and UL 98 disconnects open the circuit for service. They are not a substitute for the semiconductor fuse.

Fuses and devices for this application

Full range: High-Speed Fuses

Buyer questions

Questions buyers ask

Can a class J fuse protect the IGBTs?

Class J is a branch and feeder fuse. The semiconductors inside a drive use a high-speed fuse.

What voltage is published for square-body fuses?

Square-body and semiconductor fuses on this site are published up to 1250 Vac. Ferrule high-speed fuses are published up to 700 Vac.

Where do traction fuses fit?

High-speed traction fuses are listed with this drive range. An EV road-vehicle pack uses the EV high-speed family instead.